Company Background  |  Value,Quality & Experience  |  Marketing Objectives   |  Our Mission  |  Our Core Values  |  Financial Objectives  |  Directors

Automated 3-Phase Transformer Turns Ratio Test Set.                     
 

Item No.

Technical Description

KPLC technical Requirements

1

Physical Features

a)Portable, compact – Light weight and rugged

b)Auto selectable, with inbuilt reconfiguration software

2

Measurement Circuitry

a)Automatic, fully digital and intelligent self diagnosing

3

Test Voltage

8Vac at 1A,40Vac at 0.2A  and 100Vac at 0.1A Automatic / manually selectable

4

Excitation Current

Range

Resolution

Accuracy

0 to 1Amps

3 digits

±0.1% of reading

5

Input Power

220-230 Vac;at 50hz or Rechargeable battery with a normal 5 working hours

6

Turns- ratio measurement

Range:

Resolution

Accuracy

8Vac – 0.8 to 10,000

40Vac- 0.8 to 15,000

80/100Vac- 10 000 to

15, 000

5Digit

±0.1% of reading

7

Measurement method

ANSI/IEEE C57,12.90

8

Phase angle Measurement.

Range

Accuracy

0 – 360 degrees

±0.2% degrees

9

Test result display

Back – lit LCD Screen – Dot graphic display or laptop

10

Printing of test result

In-built printer or via computer interface

11

Printer / PC interface

RS-232C and USB port

12

PC software

Window XP professional

13

Test result storage

Can store atleast 70 transformer test plans and results

14

Accessories

One set of single phase, and extension cable,grounding,USB,RS-232c Cables and carrying case

15

Calibration

Self calibration and diagnosing

16

Interference suppression

Automatic suppression of electric and magnetic interference

17

Safety

Meets:L6101A1 and CAN/CSA C22.2 No. 1010.1-92 Certification

18

Test set operation

Independent or laptop controlled

19

Measuring time

10 to 60 seconds or less

20

 

International standards

Meets ANSI/IEEE C57.12.90 CEI/IEC 76-1;1993,ISO 9001:2000, and IEC-1010-1

21

Operating Temperature

-5ºC to 50ºC

22

Humidity

0 to 90%  Non-Condensing

23

Calibration certificate

Certificate of accredited laboratory

24

Laptop

Branded PIV running on window XP professional

25

Operating and maintenance manuals

Three in number all in English language

26

Installation

At KPLC chosen location

27

Warranty on equipment

Atleast 12months

28

Factory Inspection

Two KPLC’s Engineers

Specific Requirements.
 

1The three phase automated transformer turns ratio test set shall be capable of carrying out the following field tests on all distribution and transmission power transformers
(i)   Measure the turns ratio of the three phase simultaneously in the ranges 0.8:≥10,000 using the IEEE C57.12.90 measurement method
(ii)   Measure three phase excitation current of power transformers
(iii)   Measure the phase angle deviation between the high and low voltage windings of power transformer

3.1.2The test set shall be capable of carrying out automatic self calibration and diagnosis before and after each test

3.1.3The software shall allow for data input of the transformer turns ratio and its entire taps

3.1.4It shall be supplied with all the necessary accessories for carrying out the intended test in electrical plant and equipments

3.1.5The equipment shall be capable of testing at leased 130 different types of medium and high voltage 3-phase transformers as defined by the ANSI and IEC standards

3.1.6The power supply shall be from an internal 12Vdc rechargeable Nickel-Calcium battery or 240V ac 50Hz

 